DS Series

Type 1 / Type 2 Surge Protective Device / SPD

Login for pricing

Features:

  • UL 1449 Fourth Edition Listed
  • 100kA – 200kA per phase ratings
  • All UL required OCP & Safety Coordination included inside
    • Type 1 SPDs intended for Line or Load Side of Main Disconnect
    • Type 2 SPDs intended for Load Side of Main Disconnect
  • 20kA Inominal (In) (most models)
  • 200kA SCCRs (most models)
  • UL 96A Lightning Protection Master Label compliant (@20kA In)
  • Voltage Specific Design – highly configurable
  • All MOV suppression elements monitored
  • All Modes of Protection

Design Features

  • Designed, Manufactured & Tested consistent with:
    • ANSI/IEEE C62.41.1-2002, C62.41.2-2002, C62.45-2002, C62.62-2010 and C62.72-2007
    • NEMA LS-1
    • NEC® Article 285
    • IEC 61643
  • High Energy Parallel Design for Category C3 & C-High applications
  • For External Mounting next to Switchgear, Motor Controls Centers or Panelboards
  • Individually Fused & Thermally Protected MOVs
  • Large-Block, 34mm square, 50kA MOVs
  • Solid State Bidirectional Operation

Quality, Standards & Validation

  • Type 1: UL 1449 Fourth Edition, CSA 22.2 No. 269.1
  • Type 2 (Opt.): UL 1449 Fourth Edition, CSA No. 269.2, UL 1283
  • UL file: VZCA.E491875 at www.UL.com
  • RoHS-compliant
  • IEC 61643
  • Burn-In tested prior to shipment
  • ISO 9001:2008 Quality Management System
  • ISO 17025:2005 Laboratory Qualification

Installation, Operation & Maintenance Manual

Performance Specifications

Surge Capacities L-N L-G N-G
100kA Per Phase 50kA 50kA 50kA
200kA Per Phase 50kA 100kA 100kA
  • UL 1449 Fourth Edition Listed Type 1, CSA 22.2 No. 269.1
  • Optional UL 1449-4 Type 2 SPD, CSA 22.2 No. 269.2
  • UL 1449-4 tested Inominal (In): 20kA & 10kA
  • UL 1449-4 tested SCCR: 200kA & 100kA
  • Less than 1 nanosecond response time
  • Repetitive Impulse: 5,000 hits
  • AC Sinewave Tracking Filter with EMI/RFI Filtering up to -50dB from 10kHz to 100MHz (Type 2 option only, incl. UL 1283 Listing)
  • Physical Specifications

    • Relative Humidity Range: 0 – 95% non-condensing
    • Operating Frequency: 47 – 63Hz
    • Peak Operating Temperature: +85°C (185°F)
    • Operating Temperature: -25°C (-15°F) to +60°C (140°F)
    • Weight: 5 lbs (2.3 kg)
    • NEMA 4X Polycarbonate enclosure – UL 746C(f1) & UL 94-5VA
    • Dimensions: 6” x 6” x 4” (152mm x 152mm x 102mm) (excluding removable mounting feet)
    • Lug size: #8 – #10 AWG
    • Pre-wired with 3’ (1m) of #10 AWG conductor
    • Typical connection: 30A breaker

    Diagnostic Monitoring

    • 100% monitoring – Every MOV is monitored, incl. N-G
    • Green LED Status indicator per phase
    • Red LED service indicator
    • Phase Loss monitoring (toggles LED & dry contacts)
    • Electrically isolated circuitry ensures surges do not damage diagnostics

    Performance Data